Sizing The DOL Motor Starter Parts (Contactor, Fuse, Circuit Breaker and Thermal Overload Relay)

$
0
0
Sizing The DOL Motor Starter Parts (Contactor, Fuse, Circuit Breaker and Thermal Overload Relay)

Sizing The DOL Motor Starter Parts (Contactor, Fuse, Circuit Breaker and Thermal Overload Relay)


Calculate size of each part of DOL motor starter for the system voltage 415V, 5HP three phase house hold application induction motor, code A, motor efficiency 80%, motor RPM 750, power factor 0.8 and overload relay of starter is put before motor.


Basic Calculation of Motor Torque and Current

  • Motor Rated Torque (Full Load Torque) = 5252xHPxRPM
  • Motor Rated Torque (Full Load Torque) = 5252x5x750 = 35 lb-ft.
  • Motor Rated Torque (Full Load Torque) = 9500xKWxRPM
  • Motor Rated Torque (Full Load Torque) = 9500x(5×0.746)x750 = 47 Nm
  • If Motor Capacity is less than 30 KW than Motor Starting Torque is 3xMotor Full Load Current or 2X Motor Full Load Current.
  • Motor Starting Torque = 3xMotor Full Load Current.
  • Motor Starting Torque = 3×47 = 142Nm.
  • Motor Lock Rotor Current = 1000xHPx figure from below Chart/1.732×415

Locked Rotor Current

CodeMin.Max.
A13.14
B3.153.54
C3.553.99
D44.49
E4.54.99
F52.59
G2.66.29
H6.37.09
I7.17.99
K88.99
L99.99
M1011.19
N11.212.49
P12.513.99
R1415.99
S1617.99
T1819.99
U2022.39
V22.4
  • As per above chart Minimum Locked Rotor Current  = 1000x5x1/1.732×415 = 7 Amp
  • Maximum Locked Rotor Current = 1000x5x3.14/1.732×415 = 22 Amp.
  • Motor Full Load Current (Line) = KWx1000/1.732×415
  • Motor Full Load Current (Line) = (5×0.746)x1000/1.732×415 = 6 Amp.
  • Motor Full Load Current (Phase) = Motor Full Load Current (Line)/1.732
  • Motor Full Load Current (Phase) = 6/1.732 =4Amp
  • Motor Starting Current = 6 to 7xFull Load Current.
  • Motor Starting Current (Line) = 7×6 = 45 Amp

1. Size of Fuse

Fuse as per NEC 430-52

Type of MotorTime Delay FuseNon-Time Delay Fuse
Single Phase300%175%
3 Phase300%175%
Synchronous300%175%
Wound Rotor150%150%
Direct Current150%150%
  • Maximum Size of Time Delay Fuse = 300% x Full Load Line Current.
  • Maximum Size of Time Delay Fuse = 300%x6 = 19 Amp.
  • Maximum Size of Non Time Delay Fuse = 1.75% x Full Load Line Current.
  • Maximum Size of Non Time Delay Fuse = 1.75%6 = 11 Amp.

2. Size of Circuit Breaker

Circuit Breaker as per NEC 430-52

Type of MotorInstantaneous TripInverse Time
Single Phase800%250%
3 Phase800%250%
Synchronous800%250%
Wound Rotor800%150%
Direct Current200%150%
  • Maximum Size of Instantaneous Trip Circuit Breaker = 800% x Full Load Line Current.
  • Maximum Size of Instantaneous Trip Circuit Breaker = 800%x6 = 52 Amp.
  • Maximum Size of Inverse Trip Circuit Breaker = 250% x Full Load Line Current.
  • Maximum Size of Inverse Trip Circuit Breaker = 250%x6 = 16 Amp.

3. Thermal Overload Relay

Thermal Overload Relay (Phase):

  • Min. Thermal Overload  Relay setting = 70%x Full Load Current(Phase)
  • Min. Thermal Overload Relay setting = 70%x4 = 3 Amp
  • Max. Thermal Overload  Relay setting = 120%x Full Load Current(Phase)
  • Max. Thermal Overload Relay setting = 120%x4 = 4 Amp

Thermal Overload Relay (Phase):

  • Thermal Overload Relay setting = 100% x Full Load Current (Line).
  • Thermal Overload Relay setting = 100%x6 = 6 Amp

4. Size and Type of Contactor

ApplicationContactorMaking Cap
Non-Inductive or Slightly Inductive ,Resistive LoadAC11.5
Slip Ring MotorAC24
Squirrel Cage MotorAC310
Rapid Start / StopAC412
Switching of Electrical Discharge LampAC5a3
Switching of Electrical Incandescent LampAC5b1.5
Switching of TransformerAC6a12
Switching of Capacitor BankAC6b12
Slightly Inductive Load in Household or same type loadAC7a1.5
Motor Load in Household ApplicationAC7b8
Hermetic refrigerant Compressor Motor with Manual O/L ResetAC8a6
Hermetic refrigerant Compressor Motor with Auto O/L ResetAC8b6
Control of Restive & Solid State Load with opto coupler IsolationAC126
Control of Restive Load and Solid State with T/C IsolationAC1310
Control of Small Electro Magnetic Load ( <72VA)AC146
Control of Small Electro Magnetic Load ( >72VA)AC1510

As per above chart:

  • Type of Contactor = AC7b
  • Size of Main Contactor = 100%X Full Load Current (Line).
  • Size of Main Contactor = 100%x6 = 6 Amp.
  • Making/Breaking Capacity of Contactor = Value above Chart x Full Load Current (Line).
  • Making/Breaking Capacity of Contactor = 8×6 = 52 Amp.